The location in the data center where the VSP One Block 20 storage system will be installed must meet the following requirements:
- The location must provide sufficient clearance around the storage system for service access. In addition, there must be enough space so you can view the storage system LEDs on the front and rear panels.
Do not utilize the service clearance space for the storage of any article.
- The data center floor must have correctly positioned floor cutouts for the storage system's power and data cables. The floor cutout area and dimensions correspond to 19-inch rack specifications.
Make sure to install a grid panel of over 450 x 450 mm on the front side of the device.
The following figure shows the service clearance requirements and recommended floor cutout positions for the VSP One Block 20 storage system.