Power cable assemblies

Virtual Storage Platform G350, G370 Hardware Reference Guide

Version
88-06-0x
Audience
anonymous
Part Number
MK-97HM85012-05

For information about racks and power distribution units (PDUs), refer to the Hitachi Universal V2 Rack Reference Guide.

Hitachi power cables consist of three parts:
  • Plug Male connector for insertion into the AC outlet providing power. The physical design and layout of the plug's contact meet a specific standard.
  • Cord Main section of insulated wires of varying length, whose thickness is determined by its current rating.
  • Receptacle Female connector to which the equipment attaches. The physical design and layout of the receptacle's contacts meet a specific standard. Common standards are the IEC C13 receptacle for loads up to 10 amperes (A) and the IEC C19 receptacle for loads up to 15 A.


Number

Country or region

Voltage rating (VAC)

Current rating (amperes)

Plug type

11 North America 100-127 15 NEMA 5-15P
Brazil 200-240 10, 20 NEMA 5-15P
Japan 100-127 12 JIS C8303
Taiwan 100-127 12, 16 CNS 690
2 North America 100-127 20 NEMA 5-20P
3 North America 200-240 20 NEMA L6-20P
3 North America 200-240 30 NEMA L6-30P
42 North America 200-240 30 NEMA L15-30P
53 Hong Kong 200-240 13 BS-1363
Singapore 200-240 13 BS-1363
6 Chile 200-240 10, 16 CEI 23-50
Italy 200-240 10, 16 CEI 23-50
7 Argentina 200-240 10, 15 IRAM 2073
Australia 200-240 10, 15 AS-3112
China 200-240 10, 16 GB-1002
New Zealand 200-240 10, 15 AS-3112
8 Denmark 200-240 10 DK 2-5
Israel 200-240 10, 16 SI-32
94 Europe 200-240 CEE 7, 7
105 India 200-240 6, 16 IS-1293
South Africa 200-240 10, 16 SABS-164
11 Switzerland 200-240 10 SEV 1011
126 International 200-240 20 IEC 309
137 United Kingdom 200-240 13 BS-1363
International 200-240 20 IEC 309
148 International 200-240 30 IEC 309
Notes:
  1. Also used for 200-240 VAC applications in Korea and Philippines.
  2. Three-phase AC.
  3. Also Malaysia and Ireland.
  4. Also known as "Schuko" connector and used in Austria, Belgium, Finland, France, Germany, Greece, Hungary, Indonesia, Netherlands, Norway, Poland, Portugal, Russia, Spain, and Sweden.
  5. Supersedes type BS 546.
  6. 3-wire (two-phase and earth). Physical variations (connector size and color) indicate amperage rating. Used in Switzerland for a true 16 A application.
  7. 4-wire (three-phase and earth). Physical variations (connector size and color) indicate amperage rating.
  8. 5-wire (three-phase, earth and neutral). Physical variations (connector size and color) indicate amperage rating.