Americas three-phase PDU 3P30A-15C13-3C19-UL20A.P

Universal V3 Rack Reference Guide

Version
V3
Audience
anonymous
Part Number
MK-97RK001-03

The following figure shows the Americas three-phase PDU with 15 C13 sockets and 3 C19 sockets, and the following table provides the electrical specifications for this PDU.

Part number

Maximum number of PDUs

Power input per PDU

Power output per PDU

Total rack amperage available

Dimensions

3P30A-15C13-3C19-UL20A.P

2/side

4/rack

Three phase

208V 3P, 30A (20A rated) 60Hz

Delta/wYe: Delta

NEMA L15-30P input power plug

4.5 m (14.76 feet) cable

15 C13 + 3 C19 sockets

Max allowable current: 41.6A

14.4kVA

83.1A (28.7kVA)

Housing Length: 893 mm (35.2 in.)

Weight: 4.2 kg (9.3 lbs)