The Hitachi Universal V3 Rack can be equipped with intelligent power distribution units (iPDU) that are appropriate for the planned rack installation location: Americas, Asia-Pacific and China (APAC), or Europe-Middle East-Africa (EMEA). To maximize rack density, solutions using 60A or 400V can be used in 0U configurations. Solutions using 30A and 208V-230V connections require 1U PDUs in addition to 0U PDUs. This will reduce the useable space in the rack from 42U to 38U.
For more information, go to the following web sites:
https://www.raritan.com/why-intelligent-pdu/simplify-rack-setup-management
https://www.raritan.com/why-intelligent-pdu
https://www.raritan.com/why-intelligent-pdu/create-data-center-power-capacity
https://www.raritan.com/why-intelligent-pdu/protect-your-data-at-the-rack
Region / Type | P code | Qty per rack | Description | Rack available amperage |
---|---|---|---|---|
AMER 1P 0U AMER 1P 1U |
PX4-5884-E7 PX3-5201R |
2 4 |
iPDU 0U (12)C13 (12)Cx - 1P 30A 208V-240V AMER iPDU 1U (6)C13 (2)C19 - 1P 30A 208V-240V AMER |
72A |
AMER 3P 0U AMER 3P 2U |
PX4-534A-E7 PX3-5599R |
2 2 |
iPDU 0U (18)C13 (18)Cx - 3P 30A 208V-240V AMER iPDU 2U (12)C13 (6)C19 - 3P 30A 208V-240V AMER |
84.6A |
AMER 3P 60A 0U |
PX4-532A-E7V2 |
2 |
iPDU 0U (18)C13 (18)Cx - 3P 60A 208V-240V AMER |
84.7A |
EMEA / APAC 1P 0U EMEA / APAC 1P 1U |
PX4-5057-E7 PX3-5205R |
2 4 |
iPDU 0U (18)C13 (18)Cx - 1P 32A 230V EMEA/APAC iPDU 1U (6)C13 (2)C19 - 1P 32A 230V EMEA/APAC |
96A |
EMEA / APAC 3P 0U |
PX4-5699-E7V2 |
2 |
iPDU 0U (18)C13 (18)Cx - 3P 32A 400V EMEA/APAC |
76.8A |