The following figure shows the APAC and EMEA three-phase PDU with 24 C13 sockets and 6 C19 sockets, and the following table provides the electrical specifications for this PDU.
|
Part number |
Maximum number of PDUs |
Power input per PDU |
Power output per PDU |
Total rack amperage available |
Dimensions |
|---|---|---|---|---|---|
|
3P32A-24C13-6C19-CE20A.P |
1/side 2/rack |
Three phase 400V max. 32A (20A rated) 50Hz / 60Hz Delta/wYe: wYe CEE-plug 32A 5-poles input power plug 4.5 m (14.76 feet) cable |
24 IEC C13 + 6 IEC C19 sockets Max allowable current: 77A 50.8kVA |
77A (50.8kVA) |
Housing Length: 1376 mm (54.2 in.) Weight: 4.8 kg (10.6 lbs) |