To prevent damage to the SVP power supply, you must set the voltage selector switch to the correct voltage (115V or 230V) before you install the rack kit on the SVP.

  • Verify the onsite supply voltage that will be connected to the storage system and SVP.
  1. Remove the yellow voltage confirmation label that covers the power cord inlet on the SVP.
  2. Set the voltage selector switch to appropriate setting based on the onsite supply voltage connected to the storage system and SVP.
    • If the onsite supply voltage is 200V-240V, there is no need to remove the tamper-proof label as the default setting for the voltage selector switch is 240V. If the tamper-proof label has been removed, confirm the voltage selector switch before installing the rail kit.
    • If the onsite supply voltage is 100V-115V, remove the tamper-proof label and set the voltage selector switch to 115V before installing the rail kit.
    CAUTION:
    The voltage selector switch has a tamper-proof label covering the switch set to the default 230V setting. If this label has been removed, you must confirm the switch setting before installing the rail kit.