Upgrading compute firmware

Unified Compute Platform (UCP) Advisor Administration Guide

Version
4.5.x
Audience
anonymous
Part Number
MK-92UCP119-13
ft:lastEdition
2024-03-11

You can upgrade the compute firmware (BMC and BIOS) to the latest versions. You can also upgrade the I/O card firmware for compute nodes running an ESXi hypervisor and onboarded to the inventory using ESXi credentials. However, CPLD upgrade is not supported.

By default, the compute node powers off, which initiates operating system shutdown before the system powers off.

Note:
  • The HA800 G3 series server models are running firmware SPV 7.3, which is the latest version available.
  • CPLD upgrade support is removed from server firmware upgrade workflow.
  • For both the local site and remote site, verify that the IP addresses of the UCP Advisor VMs are reachable to the compute BMC IP address.
Note: Verify that a vCenter is registered and attached to the UCP system.
  1. Browse to the Compute inventory where you want to upgrade firmware, and then click the Refresh Compute Devices icon to refresh the inventory.
  2. Select the compute device that you want to upgrade, either in the Tile view or in the List view, and from the Actions menu, click Upgrade Firmware.

    Image showing the firmware versions for upgrading the firmware.

    Note:
    • The Upgrade Firmware option is disabled if there are no firmware bundles uploaded.
    • During the firmware upgrade task, the BMC is reset and then the firmware is upgraded. The BMC reset takes at least ten minutes to complete.
    • The I/O cards and their respective firmware details are displayed only if they were discovered before upgrading the compute firmware.
    • The SOL setting is verified before discovering the I/O cards and upgrading the firmware. If the SOL is disabled, it is enabled first, and then the I/O cards are discovered, and the firmware is upgraded. The SOL setting is restored to its original state after the I/O cards are discovered and the firmware is upgraded.
  3. Enter Submit, and then click Submit.
    For detailed information about the device and I/O card firmware versions included in the firmware bundle:
    1. Browse to Systems, select a UCP system, and then click Firmware.
    2. From the Actions list for the bundle, select View Details. The Devices, DS Series PCI Cards, and HA Series PCI Cards tabs display the firmware version details.
      View firmware details included in the firmware bundle.

You can monitor the upgrade status on the Tasks page. The firmware is upgraded sequentially for management servers, and optionally in parallel for non-management servers. During sequential upgrade of the firmware, if a server fails to upgrade, then the firmware upgrade task terminates, and the firmware on subsequent servers is not upgraded.

During a sequential upgrade or a parallel upgrade, an individual task is created for each device on the Tasks console. The Initiate Upgrade server firmware task displays the details of all the servers selected for the upgrade.

Note: For UCP systems with an external gateway, expect an approximate four-minute delay for the task to initiate while the system validates and synchronizes with UCP Advisor.

For a sequential upgrade, if the cause of the failure is specific to the server where the task terminated, reinitiate the task for the remaining servers. You can manually update the firmware on the failed server using the server's BMC UI.

Important: Running the firmware upgrade operation for more than ten servers at a time may cause the operation for some servers to time out before completing.