The table below shows the acceptable ranges for temperature, humidity, and altitude for the various HCP system components as well as an aggregate for the entire system. Operating and non-operating cases are included in the table below.
| Component | Operating temperature * | Operating humidity (non-condensing) | Altitude | Non-operating temperature | Non-operating humidity (non-condensing) |
|---|---|---|---|---|---|
| HCP system (not including storage components) |
5°C to 40°C (41°F to 104°F) |
50%-85% |
0-3000m (0-10,000 feet) |
-25°C to 70°C (-13°F to 158°F) |
20%-90% |
| HCP G11 Node |
5°C to 40°C (41°F to 104°F) |
50%-85% |
0-3000m (0-10,000 feet) |
-40°C to 70°C (-40°F to 158°F) |
20%-90% |
| Brocade ICX 6430 |
0°C to 40°C (32°F to 104°F) |
5%-95% |
0-3000m (0-10,000 feet) |
-40°C to 70°C (-40°F to 158°F) |
0%-95% |
| HP 4208VL |
0°C to 40°C (32°F to 104°F) |
15%-95% |
0-4600m (0-15,000 feet) |
-40°C to 70°C (-40°F to 158°F) |
15%-95% |
| Brocade VDX 6740 |
0°C to 40°C (32°F to 104°F) |
10%-85% |
0-3048m (0-10,000 feet) |
-25°C to 70°C (-13°F to 158°F) |
10%-90% |
| Cisco Nexus 5548 |
0°C to 40°C (32°F to 104°F) |
5%-95% |
0-3000m (0-10,000 feet) |
-40°C to 70°C (-40°F to 158°F) |
5%-95% |
| Cisco Nexus 5596 |
0°C to 40°C (32°F to 104°F) |
5%-95% |
0-3000m (0-10,000 feet) |
-40°C to 70°C (-40°F to 158°F) |
5%-95% |
| Brocade 6510 |
0°C to 40°C (32°F to 104°F) |
10%-90%- |
-60-3000m (-197-10,000 feet) |
-25°C to 70°C (-13°F to 158°F) |
10%-95% |
| Cisco MDS 9148S |
0°C to 40°C (32°F to 104°F) |
10%-90%- |
0-3000m (0-10,000 feet) |
-40°C to 70°C (-40°F to 158°F) |
10%-95% |
| * The maximum operating temperature value is specified at sea level and is derated 2.0% per 1,000 feet of increased altitude. | |||||