Install the outer server rails in the rack

Installing an HCP SAIN System - Final On-Site Setup

Version
9.7.x
File Size
41914 KB
Audience
anonymous
Part Number
MK-98ARC020-34

The two outer rails in the server rail kit attach to the sides of the rack. Each rail can attach to either side of the rack.

The outer rails are installed in the lower of the two rack units the server will occupy. For example, if the server will occupy rack units 37 and 38, the outer rails are installed in rack unit 37.

  1. At the rear of the rack, with the inside of the outer rail facing into the rack, align the two square studs at the rear of the rail with the back of the top and bottom square holes for the applicable rack unit in the vertical mounting rail.


  2. Fit the studs into the holes in the vertical mounting rail and pull the outer rail toward the rear of the rack until the back of the outer rail locks into place.


  3. At the front of the rack, align the two square studs at the front of the outer rail with the back of the top and bottom square holes for the applicable rack unit in vertical mounting rail.


  4. Fit the studs into the holes in the vertical mounting rail and pull the outer rail toward the front of the rack until the front of the outer rail locks into place.