The power connections required by the Hitachi Universal V2B Rack and Hitachi Universal V2B Rack differ by geography and input phase:
Americas
The single-phase, 208V, 30A PDUs have a NEMA L6-30P three-wire plug, as shown below.
The three-phase, 208V, 30A PDUs have a NEMA L15-30 four-wire plug, as shown below.
EMEA/APAC
The single-phase, 230V, 32A PDUs have an IEC 309 three-wire plug, as shown below.
The three-phase, 400V, 32A PDUs have an IEC 320 five-wire power plug, as shown below.
Each HCP system comes with multiple PDUs with IEC 320 C13 and IEC 320 C19 outlets. Each HCP G11 Node has two power supplies with IEC 320 C14 power inlet connectors. Each power supply connects to a PDU using a two-meter IEC 320 C13 to IEC 320 C14 power cable, as shown below. Optional Fibre Channel switches and Ethernet switches use two-meter IEC 320 C13 to IEC 320 C14 power cables.
Optional S10 nodes that come in the same rack as an HCP system plug into the IEC 320 C19 power outlets on the PDUs. Each S10 storage node has two power and cooling modules which should be connected to the PDUs using two-meter IEC 320 C19 to IEC 320 C20 power cables as shown below.