Temperature, humidity, and altitude

Installing an HCP SAIN System - Final On-Site Setup

Version
9.6.x
File Size
41843 KB
Audience
anonymous
Part Number
MK-98ARC020-33

The table below shows the acceptable ranges for temperature, humidity, and altitude for the various HCP system components as well as an aggregate for the entire system. Operating and non-operating cases are included in the table below.

Component Operating temperature * Operating humidity (non-condensing) Altitude Non-operating temperature Non-operating humidity (non-condensing)
HCP system (not including storage components)

5°C to 40°C

(41°F to 104°F)

50%-85%

0-3000m

(0-10,000 feet)

-25°C to 70°C

(-13°F to 158°F)

20%-90%
HCP G11 Node

5°C to 40°C

(41°F to 104°F)

50%-85%

0-3000m

(0-10,000 feet)

-40°C to 70°C

(-40°F to 158°F)

20%-90%
Brocade ICX 6430

0°C to 40°C

(32°F to 104°F)

5%-95%

0-3000m

(0-10,000 feet)

-40°C to 70°C

(-40°F to 158°F)

0%-95%
HP 4208VL

0°C to 40°C

(32°F to 104°F)

15%-95%

0-4600m

(0-15,000 feet)

-40°C to 70°C

(-40°F to 158°F)

15%-95%
Brocade VDX 6740

0°C to 40°C

(32°F to 104°F)

10%-85%

0-3048m

(0-10,000 feet)

-25°C to 70°C

(-13°F to 158°F)

10%-90%
Cisco Nexus 5548

0°C to 40°C

(32°F to 104°F)

5%-95%

0-3000m

(0-10,000 feet)

-40°C to 70°C

(-40°F to 158°F)

5%-95%
Cisco Nexus 5596

0°C to 40°C

(32°F to 104°F)

5%-95%

0-3000m

(0-10,000 feet)

-40°C to 70°C

(-40°F to 158°F)

5%-95%
Brocade 6510

0°C to 40°C

(32°F to 104°F)

10%-90%-

-60-3000m

(-197-10,000 feet)

-25°C to 70°C

(-13°F to 158°F)

10%-95%
Cisco MDS 9148S

0°C to 40°C

(32°F to 104°F)

10%-90%-

0-3000m

(0-10,000 feet)

-40°C to 70°C

(-40°F to 158°F)

10%-95%
* The maximum operating temperature value is specified at sea level and is derated 2.0% per 1,000 feet of increased altitude.