Temperature, humidity, and altitude

Content Platform S Series Node Help

Version
4.0.0
Audience
anonymous
Part Number
MK-HCPS027-02

The tables below show the acceptable ranges for temperature and humidity and the derating for altitude for S Series Node base and expansion enclosures under these conditions:

  • Normal operation
  • Powered off in a data center

S11 and S31 Node base enclosure and all expansion enclosures

Parameter Operating Powered off
Temperature* 5°C to 35°C (41°F to 95°F) -40°C to 70°C (-40°F to 158°F)
Relative humidity (noncondensing) 80% 100%
Altitude -100 m to 3,048 m (-328 ft to 10,000 ft) -100 m to 12,192 m (-328 ft to 40,000 ft)
*The maximum operating temperature value is specified at 900 meters and is derated 1°C per 300 meters of increased altitude (ASHRAE 2015 Class A2).

S32 Node base enclosure

Parameter Operating Powered off
Temperature* 5°C to 35°C (41°F to 95°F) -40°C to 70°C (-40°F to 158°F)
Relative humidity (noncondensing) 85% 100%
Altitude -100 m to 3,000 m (-330 ft to 10,000 ft) -100 m to 12,192 m (-328 ft to 40,000 ft)
*The maximum operating temperature value is specified at 900 meters and is derated 1°C per 300 meters of increased altitude (ASHRAE 2015 Class A2).