PDUs

Content Platform S Series Node Help

Version
4.0.0
Audience
anonymous
Part Number
MK-HCPS027-02

If your order includes both a rack and PDUs, six PDUs come already installed in the rack. If the order doesn't include a rack, the PDUs are shipped separately.

If your order doesn't include PDUs, you must supply Hitachi PDUs of the applicable type or other PDUs that meet the PDU requirements for S Series Nodes.

The Hitachi PDUs used with Hitachi Universal Racks that hold one or more S Series Nodes are the short, single-phase or three-phase PDUs. In either case, the outlets on the PDUs are single-phase. The specific PDU model used depends on the input-phase requirements, on where the S Series Node is located, and on the rack model.

PDUs for the Hitachi Universal V3 Rack

The table below shows details about the PDUs that can be used with S Series Nodes in a Hitachi Universal V3 Rack.

Geography Phase Housing length Description C13 outlets C19 outlets
Americas Single 23.4 in. (594 mm) 208V, 30A, NEMA L6-30P 10 2
Americas Three 24 in. (611 mm) 208V, 30A, NEMA L15-30 8 3
EMEA/APAC Single 21.8 in. (554 mm) 230V, 32A, IEC 309 2P+E 10 2
EMEA/APAC Three 23.5 in. (596 mm) 400V, 16A, IEC 309 3P+N+E 9 3

PDUs for the Hitachi Universal V2B Rack or Universal V2 Rack

The table below shows information about the Hitachi PDUs that can be used with S Series Nodes in a Hitachi Universal V2B Rack or Universal V2 Rack.

Geography Phase Length Description C13 outlets C19 outlets
Americas Single 24.49in (622mm) 208V, 30A, NEMA L6-30P 8 3
Americas Three 24.49in (622mm) 208V, 30A, NEMA L15-30 8 3
EMEA/APAC Single 23.46in (596mm) 230V, 32A, IEC309 2P+E 9 3
EMEA/APAC Three 23.46in (596mm) 400V, 16A, IEC309 3P+N+E 9 3