If your order includes both a rack and PDUs, six PDUs come already installed in the rack. If the order doesn't include a rack, the PDUs are shipped separately.
If your order doesn't include PDUs, you must supply Hitachi PDUs of the applicable type or other PDUs that meet the PDU requirements for S Series Nodes.
The Hitachi PDUs used with Hitachi Universal Racks that hold one or more S Series Nodes are the short, single-phase or three-phase PDUs. In either case, the outlets on the PDUs are single-phase. The specific PDU model used depends on the input-phase requirements, on where the S Series Node is located, and on the rack model.
PDUs for the Hitachi Universal V3 Rack
The table below shows details about the PDUs that can be used with S Series Nodes in a Hitachi Universal V3 Rack.
Geography | Phase | Housing length | Description | C13 outlets | C19 outlets |
---|---|---|---|---|---|
Americas | Single | 23.4 in. (594 mm) | 208V, 30A, NEMA L6-30P | 10 | 2 |
Americas | Three | 24 in. (611 mm) | 208V, 30A, NEMA L15-30 | 8 | 3 |
EMEA/APAC | Single | 21.8 in. (554 mm) | 230V, 32A, IEC 309 2P+E | 10 | 2 |
EMEA/APAC | Three | 23.5 in. (596 mm) | 400V, 16A, IEC 309 3P+N+E | 9 | 3 |
PDUs for the Hitachi Universal V2B Rack or Universal V2 Rack
The table below shows information about the Hitachi PDUs that can be used with S Series Nodes in a Hitachi Universal V2B Rack or Universal V2 Rack.
Geography | Phase | Length | Description | C13 outlets | C19 outlets |
---|---|---|---|---|---|
Americas | Single | 24.49in (622mm) | 208V, 30A, NEMA L6-30P | 8 | 3 |
Americas | Three | 24.49in (622mm) | 208V, 30A, NEMA L15-30 | 8 | 3 |
EMEA/APAC | Single | 23.46in (596mm) | 230V, 32A, IEC309 2P+E | 9 | 3 |
EMEA/APAC | Three | 23.46in (596mm) | 400V, 16A, IEC309 3P+N+E | 9 | 3 |